Article

Energy Performance of 3D-Printed Concrete Walls: A Numerical Study

by
Thadshajini Suntharalingam
1,
Irindu Upasiri
2,
Perampalam Gatheeshgar
1,
Keerthan Poologanathan
1,*,
Brabha Nagaratnam
1,
Paulo Santos
3 and
Heshachanaa Rajanayagam
1
1
Department of Mechanical and Construction Engineering, Faculty of Engineering and Environment, Northumbria University, Newcastle upon Tyne NE1 8ST, UK
2
Department of Civil Engineering, Faculty of Engineering, University of Sri Jayewardenepura, Ratmalana 10390, Sri Lanka
3
ISISE, Department of Civil Engineering, University of Coimbra, 3030-788 Coimbra, Portugal
*
Author to whom correspondence should be addressed.
Submission received: 16 August 2021 / Revised: 15 September 2021 / Accepted: 21 September 2021 / Published: 25 September 2021
(This article belongs to the Section Building Structures)

Abstract

:
Three-dimensional-printed concrete (3DPC), which is also termed as digital fabrication of concrete, offers potential development towards a sustainable built environment. This novel technique clearly reveals its development towards construction application with various global achievements, including structures such as bridges, houses, office buildings, and emergency shelters. However, despite the enormous efforts of academia and industry in the recent past, the application of the 3DPC method is still challenging, as existing knowledge about its performance is limited. The construction industry and building sectors have a significant share of the total energy consumed globally, and building thermal efficiency has become one of the main driving forces within the industry. Hence, it is important to study the thermal energy performance of the structures developed using the innovative 3DPC technique. Thermal characterization of walls is fundamental for the assessment of the energy performance, and thermal insulation plays an important role in performance enhancements. Therefore, in this study, different wall configurations were examined, and the conclusions were drawn based on their relative energy performance. The thermal performance of 32 different 3DPC wall configurations with and without cavity insulation were traced using validated finite element models by measuring the thermal transmittance value (U-value). Our study found that the considered 3DPC cavity walls had a low energy performance, as the U-values did not satisfy the standard regulations. Thus, their performance was improved with cavity insulation. The simulation resulted in a minimum thermal transmittance value of 0.34 W/m2·K. Additionally, a suitable equation was proposed to find the U-values of 100 mm-thick cavity wall panels with different configurations. Furthermore, this study highlights the importance of analytical and experimental solutions as an outline for further research

1. Introduction

The future sustainability of the built environment and the significant potential contribution of energy-efficient buildings have become crucial concerns nowadays. The construction industry is one of the sectors that requires substantial improvements to reduce its adverse effects on the environment and climate change [1,2]. This industry has a great influence on the environment in its energy utilization, as it uses more than 50% of all raw material globally, releases the largest amount of carbon, and is accountable for 40% of total energy consumed globally [1,3,4,5,6]. Hence, the perception of sustainable development in the construction industry is gaining attention, with increasing awareness of environmental protection laws. A built environment with minimized energy consumption has become the prime objective these days. In order to achieve this, new development practices, resources, and approaches are being pursued by current industries and researchers [7]. In addition to energy efficiency, lightweight material also provides sustainability by means of reducing material costs and related emissions incurred throughout the production. Hence, there is a necessity to use some regulations and initiatives to achieve these interests to enhance the energy efficiency in buildings [8].

1.1. Three-Dimensional-Printed Concrete (3DPC) and Sustainability

Over the past decade, the interest in the pursuit on extrusion-based 3D-printed concrete (3DPC) has been increasing exponentially. This innovative technology has been recognized as a sustainable green construction and environmentally friendly solution, as it reduces the overall construction waste and costs [9,10,11,12]. The integration of 3DPC in the design and construction of built environments brings many promising advantages, such as minimal manpower and labor costs, rapid fabrication, reduction of construction wastes, cost-effectiveness, formwork-free construction, and increased flexibility with precise architectural design. In addition to conventional building components, entirely unique and complex configurations, which are not viable with conventional formwork, can be constructed using 3DPC [10,12,13,14,15]. In addition, 3DPC provides lesser self-weight structures with topology optimization, and further reduction of weight and enhanced thermal insulation properties could be achieved by developing mix designs using materials with low thermal conductivity [16,17]. While 3DPC is regarded as a revolutionizing and innovative manufacturing technology, the creative conception and application of such a technology is still underexplored. Moreover, to fully utilize such a new technique, a deeper understanding of the process, from the design phase to the postprocessing phase, is required. However, researchers are focusing more on the structural performance of 3DPC structures, and numerous research studies are ongoing worldwide [18,19,20,21,22].

1.2. Types of 3DPC Cavity Structures

The 3DPC technique offers design flexibility with the inclusion of air cavities in the wall panels while satisfying both structural and thermal performance criteria. Different cavity provisions will also influence the thermal behaviour of the overall structure due to the concurrent occurrence of conduction, convection, and radiation heat-transfer processes [23]. Therefore, the printing parameters should be chosen wisely in order to achieve sustainable and energy-efficient 3DPC structures. Currently, 3DPC wall panels with different thicknesses and cross-sectional arrangements are used in the industry for better thermal and acoustic characteristics. Figure 1 shows some of the actual 3DPC wall panels with different cross-sectional geometries that have been developed to be structurally stable. Wang et al. [24] developed a systematic approach to explore optimization of the mechanical capacity of 3DPC cavity structural elements with different internal cross sections. Beam elements have four different types of interior cavity structures: cellular-shaped, truss structure, lattice-shaped structure with a square topology, and grid-shaped structure with triangular topology. Figure 2 shows the wall configurations studied structurally by Wang et al. [24].

1.3. Energy Efficiency of 3D-Printed Concrete Structures

Many design guidelines and performance criteria are available for the thermal performance of normal concrete, whereas very few studies have evaluated the thermal energy behaviour of 3DPC structures to date. The standard approach to determine the energy performance is the quantification of the thermal transmittance value (U-value), which is extensively used in Europe [2,23]. The thermal transmittance is a measure of how much heat will pass through one square metre of a structure when the air temperatures on either side differ by one degree (W/m2·K). The U-value depends on the thermal conductivity (λ) of the material and its thickness (d): U = λ/d. Therefore, lower U-values or higher energy performances signify better levels of thermal insulation.
The ability to take precise measurements of the appropriate thermal performance is essential to understand and improve the thermal efficiency of this new 3DPC technology. The thermal performance of the exterior walls greatly influences the energy consumption of buildings and consequently their efficiency, as well as their emission of greenhouse gases [2,29]. In addition, the overall energy performance of a structure depends on external walls and their insulating value, and represents approximately 25% of the total heat loss [3]. The thermal performance, thickness, and properties of the materials used in these wall components play a significant role in regulating the heat loss and gain of the building [2,23,30]. The introduction of air gaps and filling the cavity using insulation materials or insulation layers between the structural elements is an effectual technique to attain the required thermal comfort of a building [31]. In addition, by enhancing the thermal insulating properties of the external walls, enhancements in construction sustainability can be also accomplished.
While energy-saving building features have been integrated into the design of 3DPC elements, there has not been a systematic study on the energy efficiency of 3DPC buildings. Pessoa et al. [29] conducted a systematic literature review to identify the key innovations made so far in 3DPC technology and its applicability in the construction industry, with specific attention being given to the thermal efficiency. Alkhalidi and Hatuqay [31] investigated and developed energy-efficient and low-cost residential 3DPC elements that could be accomplished through a green and sustainable method. Similarly, He et al. [32] introduced a 3DPC modular building system with an integrated vertical greenery system called the 3D-printed vertical green wall (3D-VtGW). Moreover, Craveiro et al. [33] experimentally analyzed the structural and thermal performances of several printable materials, including normal concrete, concrete mixed with cork, and concrete mix with expanded clay. Furthermore, Cuevas et al. [16] developed a 3D-printed lightweight concrete mixture with waste glass as an aggregate with lower density, and achieved a 40% reduction in thermal conductivity. Al-Ghamdi [7] conducted a detailed experimental study to examine the effects of different printing parameters to lower the energy consumption and printing period, and to ensure lightweight construction of acrylonitrile butadiene styrene (ABS) components through extrusion-based 3D printing. In addition, Marais et al. [30] numerically investigated the thermal performance of 3DPC structures with macrostructural cavity arrangements using lightweight foam concrete and high-performance concrete. However, there is still an obvious lack of investigations of the thermal energy performance of 3DPC structures to date, and there is a need to examine the thermal performance from a unique perspective.

1.4. Scope of the Current Study

In view of above discussion, the aim of the present study was to analyze the energy performance of 3DPC wall panels with different configurations and insulation materials. Complying with currently available geometries of 3DPC walls in the industry and the cavity arrangements proposed by Wang et al. [24], this study numerically investigated the energy performance of the innovative 3DPC wall configurations. Suitable heat transfer numerical models with cavity wall configurations proposed by Alkhalidi and Hatuqay [31] were developed using Abaqus [34] finite element software. The models were then validated by comparing the U-value results presented by Alkhalidi and Hatuqay [31]. The study was then extended with a detailed parametric study of 32 analyses by varying two different printing parameters, namely wall configurations and insulation material. The numerical analysis performed on the study revealed that the considered parameters had a significant influence on the energy efficiency of 3DPC wall panels. Finally, a suitable wall configuration with cavity insulation was proposed in order to ensure an energy-efficient and sustainable 3DPC wall panel development process. Furthermore, using the numerical analysis, a simple equation was also derived to determine the U-value of complex cavity geometries without using FE modelling. This study offers a vision to the future investigation of energy-efficient, complex 3DPC structures that can be utilized in the construction industry.

2. Development of the Finite Element Model

This section explains the development of the three-dimensional finite element (FE) model for analysing the energy performance of 3DPC wall panels with different cross-sectional arrangements. The U-value is the thermal transmittance of the wall configuration. It has a direct relationship with the element’s thermal performance; if the U-value is low, it implies that the wall’s thermal performance is better. U-value (U) has an inverse relationship with thermal resistance ( R T ) of the element (Equation (1)). The thermal resistance of the element depends on the internal surface thermal resistance ( R si ), external surface thermal resistance ( R se ), and the element layer resistance ( R ) (Equation (2)). Further heat flux and the temperature variation between the external and internal surfaces has a relationship with the U-value (Equation (3)). Thermal resistance has a co-relationship with the thermal conductivity ( λ ) and the thickness of the layer (d) as expressed in Equation (4). If a wall configuration is available with different layers of materials using Equation (2), the U-value of the wall configuration could be easily determined. However, instead of layers, the combination of materials was in complex shapes in the 3DPC wall configurations considered in this study, and thus a direct equation could not be used. Therefore, a numerical analysis was utilized in determining the U-values of the analysed wall configurations.
U = 1 R T
R T = R si + R + R se
Heat   Flux = Temperature   Difference × ( U Value )
R = d λ
The examination of overall thermal performance of a structure is known as coupled analysis, which investigates the combined mechanical–thermal behaviour. Due to the lack of experimental investigations, non-load-bearing 3DPC wall configurations were considered in this study, and uncoupled heat-transfer analysis was performed. Hence, the developed models were incapable of simulating the structural behaviour or the fracture of the wall. Therefore, three-dimensional heat-transfer analysis was conducted to determine the 3DPC wall configurations’ thermal transmittance; the steady-state heat transfer depended on the thermal conductivity of the material. The thermal conductivities of the concrete mixture used for the 3DPC cavity wall panels and the cavity insulation material, expanded polylactic acid (E-PLA), were obtained from the study performed by Alkhalidi and Hatuqay [31]. External and internal temperature boundary conditions were set to 0 °C and 40 °C, respectively. The convective surface heat-transfer coefficients were set according to EN ISO 6946: 25 W·m−2·K−1 and 7.69 W·m−2·K−1 for the external and internal environment, respectively. Two surface film condition interactions were defined separately in the external and internal surfaces to achieve these boundary conditions in the developed FE model. For the external surface film, a coefficient of 25 W·m−2·K−1 was set with a sink temperature of 0 °C; whereas for the internal surface film, a coefficient of 7.69 W·m−2·K−1 was set with a sink temperature of 40 °C. Heat-transfer elements (DC3D8 elements) were used in meshing the model. Global seeding of 10 mm and edge seeding of 2 mm was achieved through the thickness as mesh sizes, and steady-state heat-transfer analysis was conducted. Heat-flux results were obtained as a result of the analysis, and based on the Equation (3), U-values were calculated, dividing the average heat flux from the temperature difference (40 °C). The cavity of the configurations was modelled as air layers. Air thermal transmittance was considered as 0.18 m2·K/W, and considering the relationship given in Equation (4), air thermal conductivity (λc) was calculated based on the thickness of the air layer. The geometry modelling, applying boundary conditions, applying tie constraints, and meshing of one of the wall configurations, are shown in Figure 3a–c.

3. Validation of the Developed FE Model

Validation of the developed simulation was essential to evaluate the accuracy of the implemented models, the assumed simplifications for the model applications, and the material characterization. Hence, all developed simulation models were validated against previously published literature. The U-values results obtained from the finite element analysis (FEA) using Abaqus were compared with the results presented by Alkhalidi and Hatuqay [31], who calculated the U-value of the wall configurations with air gap and cavity filled with expanded polylactic acid (E-PLA). Five different 3DPC wall arrangements with three different materials were used in this study. Hence, 30 models were validated in total. Three material mixes were selected with recyclable contents with excellent thermal properties. The first tested mix was a sulphur concrete mix, the second was a cork concrete, and the third was composed of powdered silica sand with an organic binder. The thermal properties of the concrete mixes are presented in Table 1, and the thermophysical properties of air and E-PLA are given in Table 2. The wall panel arrangements used for the validation are illustrated in Figure 4.
The comparison of results of three different mixes (Mix 1, Mix 2, and Mix 3) of 3DPC are shown in Figure 5a–c. The U-value curves of wall configurations presented by Alkhalidi and Hatuqay [31] showed excellent agreement with the FEA results, hence the Abaqus simulations were accurate and reliable. Since the U-values results matched, we concluded that the developed FE models could be utilized for detailed parametric analysis of the energy performance of 3DPC walls.

4. Parametric Study

Currently, 3D-printed solid wall panels with different thicknesses are used in industry for improved thermal and acoustic characteristics. When the increasing wall thickness, energy, and acoustic performance are enhanced, however, material costs and carbon footprint are increased. The most crucial problem with wide concrete wall panels is the challenging nature of handling the panels at the construction site, due to their heavy weight. Complying with currently available 3DPC wall panels in the industry and the wall configurations proposed by Wang et al. [24], eight (8) innovative cavity wall configurations were chosen to observe the effect of thickness of the wall panels, cross-sectional configurations, and the thermal insulation on the energy performance. Mix 3 from the study by Alkhalidi and Hatuqay [31] was selected for this parametric study due to its better energy performance with lower U-values; the properties of this printable concrete are presented in Table 1. In this study, a heat-transfer analysis was conducted on wall panels with thicknesses of 100 mm and 12 mm layer thickness, and wall thicknesses of 200 mm with 25 mm layer thickness. The nozzle sizes were selected based on the actual constructed structures. The walls were developed to be 1 m long and 1 m high with different cross-sectional arrangements. The parametric study included 32 wall specimens of eight different single- and double-row cross-sectional arrangements, with and without cavity insulation. The details of the parametric study are presented in Table 3. The analysed different configurations details are shown in Table 4. The same wall panels also were analysed with E-PLA cavity insulation.

5. Results and Discussion

This section describes the numerical simulation results derived for the considered wall configurations for energy performance and the variation of thermal transmittance value (U-values). The measured U-values of each wall configuration is given in Table 5. The effect of wall thickness and the cross-sectional configurations with the void area are discussed extensively herein.

5.1. Effect of Wall Thickness with Different Configurations

Figure 6 shows the variation of U-value for the considered 100 mm and 200 mm thickness wall configurations without cavity insulation. It is clear that the U-value mostly decreased with increased wall thickness regardless of the cross-sectional configurations, except the double-row lattice configuration (C6200). Moreover, C1, C2, and C3 were developed with single-row cross-sectional configurations, and the C4–C8 wall panels were developed with double rows (Table 4). Hence, a significant reduction in the U-value was identified for the 100 mm double-row wall panels compared to the single-row panels. However, there was a fluctuating trend identified for the 200 mm wall configurations.
In terms of different cross-sectional configurations, higher intermediate barriers caused a reduction in material conductivities; hence, an increased thermal efficiency was obtained. In both single- and double-row 100 mm breadth wall panels, the triangular shaped panels displayed a higher performance, with lower U-values compared to other configurations. However, lattice-shaped wall panels showed a higher reduction in the U-value of approximately 40% when increasing the midway partitions with an additional row. The 200 mm thickness wall panels with triangular and sinusoidal shapes also showed a similar percentage of reduction, whereas the lattice-shaped wall panels behaved contrarily. The reduction in U-values due to increasing intermediate barriers with an additional row is listed in Table 6. However, these values derived for thermal transmittance were considerably higher than the required standard values. Hence, expanded polylactic acid (E-PLA) was used as thermal insulation material, and the U-values were assessed again. E-PLA is a lightweight sustainable material that has similar properties to expanded polystyrene.

5.2. Effect of Cavity Insulation

Figure 7 illustrates the U-values obtained from the analysis for the selected 100 mm wall configurations with and without cavity insulation. The incorporation of E-PLA material as the insulation reduced the U-value, and thus increased the thermal performance of the wall panels for all the configurations. However, single-row wall configurations achieved relatively higher reductions in U-value compared to some of the double row wall configurations which contradicted the results presented by Alkhalidi and Hatuqay [31]. Hence, there was an obvious relationship for U-values with the volume of the cavity and insulation, which must be examined further.
In relation to the cross-sectional arrangements, single-row lattice and sinusoid and double-row sinusoidal arrangements exhibited a higher energy performance, while those filled with E-PLA had U-values in the range of 0.64–0.69 W/m2·K. Conversely, triangular-shaped wall panels showed a relatively lower performance with an increased midway row. The reductions in U-values due to the incorporation of insulation material is presented in Table 7. Still, these values of thermal transmittance were noticeably higher than the required standard values. Hence, the 200 mm thickness wall panels were examined to further reduce the U-values while increasing the performance.
Figure 8 depicts the U-value results derived for 200 mm wall configurations with and without E-PLA insulation. The cavity insulation with E-PLA material had significantly reduced U-values. Moreover, approximately similar U-values were attained for all the wall configurations irrespective of single- and double-row arrangements. This scenario must be further investigated with respect to cavity volume.
From Figure 8, it is apparent that the wall with double-row lattice arrangement had a lower U-value of 0.34 W/m2·K with E-PLA insulation. All three single-row wall configurations and double-row sinusoidal arrangements also showed better energy performance when filled with E-PLA, with U-values in the range of 0.45–0.50 W/m2·K. Similar to 100 mm wall panels, double-row, triangular-shaped wall panels showed a comparatively lower performance with increased intermediate barriers. Furthermore, Figure 9 shows the variation in U-values for all the wall panels studied with and without cavity insulation. An evident reduction in U-values was observed with cavity insulation for both the 100 mm and 200 mm thickness wall panels. Moreover, 100 mm wall panels with E-PLA exhibited lower U-values compared to 200 mm cavity walls, except both double-row triangular cross-sectional wall panels. However, the U-values were nearly identical for single-row wall configurations and the double-row sine-curved wall panels regardless of the wall thickness when cavity-insulated. The reduction percentages of the U-values due to the incorporation of insulation material are presented in Table 7.
Wall configurations with double-row triangular arrangements did not attain a noticeable reduction in U-values with the integration of E-PLA insulation. Observed reductions in U-values were nearly 23% and 28% for 100 mm and 200 mm wall panels, respectively. However, all the other wall configurations attained a significant improvement in energy performance with E-PLA insulation. The measured reduction in U-values for the single-row triangular, lattice, and sinusoid wall arrangements with insulation ranged around 60–70%, which clearly showed the connectivity with the void area and energy performance with the integration of insulation material. In addition, the C6200 (double-row lattice arrangement), which had the highest U-value of 2.17 W/m2·K. among the 200 mm wall panels, achieved a lower U-value of 0.34 W/m2·K with E-PLA insulation, with higher performance compared to all the other configurations. Hence, the variation of U-value with the void area was studied to further understand the behaviour of the considered wall configurations. Since the thermal conductivity of void air changes with the thickness, only the variation in U-values with E-PLA insulation was investigated.

5.3. Variation of U-Values with Cavity Area

As shown in Figure 10, the U-value was relatively decreased with an increased void area with insulation. A larger amount of insulation directed a reduction in material conductivities; hence, the best thermal efficiency was achieved. However, with the different cross-sectional arrangements and variations in thermal transmittance path, fluctuating behaviour was identified. However, the 200 mm wall panels, such as single-row triangular (C1200), lattice (C2200), sinusoid (C3200), and double-row lattice (C6200) and sinusoid (C7200, C18200) showed improved performances with E-PLA insulation. Figure 11 and Figure 12 display the heat-flux variation along the wall panels for 100 mm and 200 mm, respectively.
Thermal bridging can be observed through concrete, as shown in the contour plots in Figure 11 and Figure 12. Thermal conductivity was approximately 10 times higher in concrete than in air or E-PLA (Table 1 and Table 2), which created a thermal bridge from the concrete. However, this study did not consider any particular relative humidity condition in determining the dew point. The study intended to emphasize the effect of different configurations on the thermal performance (U-value) with air voids and with insulation material filling. Any interested user can use the study results and, by using standard relationships, could calculate the dew point with available relative humidity.

6. Proposal of Equation for the Estimation of U-Value of 3DPC Cavity Walls

The theoretical equation to calculate the U-value of a wall panel is given in Equation (1). This equation can be directly used for rectangular columns having different layers of materials. However, it cannot be directly used for 3DPC walls, since the walls’ geometry is complex. The development and analysis of FE modelling was used for determining the U-value of the complex-shaped 3DPC walls in this study. However, FE modelling takes time and requires expert knowledge in FE modelling techniques. Therefore, a simple equation was derived to determine the U-values of the 3DPC cavity walls with complex geometries. From the above analysis, it was identified that the thermal conductivity of cavity and concrete and the cross-sectional area of concrete panel and the cavity had a clear influence on the thermal energy performance of the 3DPC wall configurations. Hence, Equation (5) is proposed to calculate the U-values of 100 mm thickness cavity wall panels with different cross-sectional arrangements with the aforementioned parameters. The U-values calculated using the proposed equation were compared with FE results, and are illustrated below in Table 8. The mean and COV values of comparison were calculated, and were 1.0 and 0.02, respectively. Therefore, the equation gave the best prediction of FE values for the U-values, and thus the thermal behaviour of 100 mm thickness cavity wall panels. However, further analysis must be performed to determine a similar kind of relationship for U-values with these parameters for wall panels with different thicknesses and cavity insulation.
U value = λ c λ s λ s ( A c L w ) + λ c ( A T A C ) L w

7. Conclusions

The 3DPC technology used here is a developing construction method at present, and its applications are currently being subjected to many research studies. However, not enough research has been conducted to identify the appropriateness of these innovative construction technologies, and there is an ongoing controversy as to whether they are an appropriate replacement for traditional construction techniques. Moreover, there is a clear absence of investigations on the energy performance of 3DPC wall panels. Hence, this study investigated the energy performance of 3DPC wall configurations using numerical simulations. A series of 32 simulations with different 3DPC wall configurations were performed, aiming to determine the U-values. Based on the simulation results, the following conclusions were drawn:
  • U-values of cavity walls generally decreased with increased wall thickness, regardless of the cross-sectional configurations;
  • A significant reduction in the U-value was recognized for 100 mm wall panels with an additional intermediate row compared to single-row panels;
  • Triangular-shaped cavity wall panels of 100 mm thickness displayed the highest performance, with lower U-values compared to other configurations. Double-row triangular and sinusoid-shaped 200 mm thickness cavity wall panels showed higher performance compared to other walls. However, the U-values were noticeably higher than the standard values. Thus, expanded polylactic acid (E-PLA) was used as thermal insulation material to enhance the performance;
  • The incorporation of E-PLA material as the insulation reduced the U-value, and thus increased the thermal performance of the wall panels for all the configurations;
  • The lowest obtained thermal transmittance value in this study was 0.34 W/m2·K, for the 200mm thickness wall configuration with a double-row lattice arrangement with E-PLA insulation (C6200);
  • There was an evident relationship with void area and energy performance of 3DPC walls with the integration of insulation material;
  • An equation was proposed to determine the U-values of 100 mm thickness cavity wall panels with complex cross-sectional configurations without using FE modelling.
This study is the first step towards enhancing the understanding of the thermal energy performance of 3DPC walls. However, the influence on fire and structural performance has not been analysed yet. Hence, further studies on different mixes and cavity-filling materials could be performed for further optimization.

Author Contributions

Conceptualization: K.P.; performed the numerical simulations and analysis: I.U. and T.S.; results interpretation: I.U., T.S., and K.P.; writing—original draft preparation: T.S., I.U. and P.G.; writing—review and editing: T.S., I.U., P.G., K.P., B.N. and P.S.; visualization: T.S. and H.R.; supervision: K.P. and B.N. All authors have read and agreed to the published version of the manuscript.

Funding

This research study is funded by Research Development Fund (RDF), Northumbria University.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Acknowledgments

The authors would like to acknowledge the financial and technical support of Northumbria University and University of Sri Jayewardenepura.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Di Foggia, G. Energy efficiency measures in buildings for achieving sustainable development goals. Heliyon 2018, 4, e00953. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  2. Santos, P.; Gonçalves, M.; Martins, C.; Soares, N.; Costa, J.J. Thermal transmittance of lightweight steel framed walls: Experimental versus numerical and analytical approaches. J. Build. Eng. 2019, 25, 100776. [Google Scholar] [CrossRef]
  3. Lima, L.; Trindade, E.; Alencar, L.; Alencar, M.; Silva, L. Sustainability in the construction industry: A systematic review of the literature. J. Clean. Prod. 2020, 289, 125730. [Google Scholar] [CrossRef]
  4. Murtagh, N.; Scott, L.; Fan, J. Sustainable and resilient construction: Current status and future challenges. J. Clean. Prod. 2020, 268, 122264. [Google Scholar] [CrossRef]
  5. Yüksek, I.; Karadayi, T.T. Energy-Efficient Building Design in the Context of Building Life Cycle. Energy Effic. Build. 2017, 1–20. [Google Scholar] [CrossRef] [Green Version]
  6. Lohmann, V.; Santos, P. Trombe Wall Thermal Behavior and Energy Efficiency of a Light Steel Frame Compartment: Experimental and Numerical Assessments. Energies 2020, 13, 2744. [Google Scholar] [CrossRef]
  7. Al-Ghamdi, K.A. Sustainable FDM additive manufacturing of ABS components with emphasis on energy minimized and time efficient lightweight construction. Int. J. Light. Mater. Manuf. 2019, 2, 338–345. [Google Scholar] [CrossRef]
  8. Jacobs, J. Concrete for Energy-Efficient Buildings, The Benefits of Thermal Mass; European Concrete Platform: Brussels, Belgium; British Cement Association: Camberley, UK ; British Ready-Mixed Concrete Association: London, UK; British Precast Concrete Federation: Glenfield, UK; The Cement Admixtures Association: Solihull, UK, 2007. [Google Scholar]
  9. Paul, S.C.; Van Zijl, G.P.; Tan, M.J.; Gibson, I. A review of 3D concrete printing systems and materials properties: Current status and future research prospects. Rapid Prototyp. J. 2018, 24, 784–798. [Google Scholar] [CrossRef] [Green Version]
  10. Al Rashid, A.; Khan, S.A.; Al-Ghamdi, S.G.; Koç, M. Additive manufacturing: Technology, applications, markets, and opportunities for the built environment. Autom. Constr. 2020, 118, 103268. [Google Scholar] [CrossRef]
  11. Luhar, S.; Suntharalingam, T.; Navaratnam, S.; Luhar, I.; Thamboo, J.; Poologanathan, K.; Gatheeshgar, P. Sustainable and Renewable Bio-Based Natural Fibres and Its Application for 3D Printed Concrete: A Review. Sustainability 2020, 12, 10485. [Google Scholar] [CrossRef]
  12. Khan, S.A.; Koç, M.; Al-Ghamdi, S.G. Sustainability assessment, potentials and challenges of 3D printed concrete structures: A systematic review for built environmental applications. J. Clean. Prod. 2021, 303, 127027. [Google Scholar] [CrossRef]
  13. Chen, Y.; Çopuroğlu, O.; Rodriguez, C.R.; Filho, F.F.D.M.; Schlangen, E. Characterization of air-void systems in 3D printed cementitious materials using optical image scanning and X-ray computed tomography. Mater. Charact. 2021, 173, 110948. [Google Scholar] [CrossRef]
  14. Ooms, T.; Vantyghem, G.; Van Coile, R.; De Corte, W. A parametric modelling strategy for the numerical simulation of 3D concrete printing with complex geometries. Addit. Manuf. 2021, 38, 101743. [Google Scholar] [CrossRef]
  15. Nguyen-Van, V.; Panda, B.; Zhang, G.; Nguyen-Xuan, H.; Tran, P. Digital design computing and modelling for 3-D concrete printing. Autom. Constr. 2021, 123, 103529. [Google Scholar] [CrossRef]
  16. Cuevas, K.; Chougan, M.; Martin, F.; Ghaffar, S.H.; Stephan, D.; Sikora, P. 3D printable lightweight cementitious composites with incorporated waste glass aggregates and expanded microspheres—Rheological, thermal and mechanical properties. J. Build. Eng. 2021, 44, 102718. [Google Scholar] [CrossRef]
  17. Song, J.; Cao, M.; Cai, L.; Zhou, Y.; Chen, J.; Liu, S.; Zhou, B.; Lu, Y.; Zhang, J.; Long, W.; et al. 3D printed polymeric formwork for lattice cementitious composites. J. Build. Eng. 2021, 43, 103074. [Google Scholar] [CrossRef]
  18. Baduge, S.K.; Navaratnam, S.; Abu-Zidan, Y.; McCormack, T.; Nguyen, K.; Mendis, P.; Zhang, G.; Aye, L. Improving performance of additive manufactured (3D printed) concrete: A review on material mix design, processing, interlayer bonding, and reinforcing methods. Structures 2021, 29, 1597–1609. [Google Scholar] [CrossRef]
  19. Hou, S.; Duan, Z.; Xiao, J.; Ye, J. A review of 3D printed concrete: Performance requirements, testing measurements and mix design. Constr. Build. Mater. 2021, 273, 121745. [Google Scholar] [CrossRef]
  20. Xiao, J.; Liu, H.; Ding, T. Finite element analysis on the anisotropic behavior of 3D printed concrete under compression and flexure. Addit. Manuf. 2021, 39, 101712. [Google Scholar] [CrossRef]
  21. Suiker, A. Mechanical performance of wall structures in 3D printing processes: Theory, design tools and experiments. Int. J. Mech. Sci. 2018, 137, 145–170. [Google Scholar] [CrossRef] [Green Version]
  22. Panda, B.; Lim, J.H.; Tan, M.J. Mechanical properties and deformation behaviour of early age concrete in the context of digital construction. Compos. Part B Eng. 2019, 165, 563–571. [Google Scholar] [CrossRef]
  23. Santos, P.; Lemes, G.; Mateus, D. Thermal Transmittance of Internal Partition and External Facade LSF Walls: A Parametric Study. Energies 2019, 12, 2671. [Google Scholar] [CrossRef] [Green Version]
  24. Wang, L.; Jiang, H.; Li, Z.; Ma, G. Mechanical behaviors of 3D printed lightweight concrete structure with hollow section. Arch. Civ. Mech. Eng. 2020, 20, 1–17. [Google Scholar] [CrossRef] [Green Version]
  25. 3D Printed Building in SIP. [image]. Available online: http://www.sipac.gov.cn/english/categoryreport/IndustriesAndEnterprises/201611/t20161129_506766.htm (accessed on 13 April 2021).
  26. INNOVATIVE METHODS FOR REINFORCED CONCRETE. [image]. Available online: https://www.etesias.it/en/about-en.html (accessed on 15 April 2021).
  27. Gosselin, C.; Duballet, R.; Roux, P.; Gaudillière, N.; Dirrenberger, J.; Morel, P. Large-scale 3D printing of ultra-high performance concrete—A new processing route for architects and builders. Mater. Des. 2016, 100, 102–109. [Google Scholar] [CrossRef] [Green Version]
  28. Piroozfar, A.E.; Larsen, O.P.; Altan, H.; Piller, F.T.; Tseng, M.M. Customization in Building Design and Construction: A Contribution to Sustainability. In Handbook of Research in Mass Customization and Personalization; World Scientific Pub Co Pte Lt.: London, UK, 2009; pp. 911–939. [Google Scholar]
  29. Pessoa, S.; Guimarães, A.; Lucas, S.; Simões, N. 3D printing in the construction industry - A systematic review of the thermal performance in buildings. Renew. Sustain. Energy Rev. 2021, 141, 110794. [Google Scholar] [CrossRef]
  30. Marais, H.; Christen, H.; Cho, S.; De Villiers, W.; Van Zijl, G. Computational assessment of thermal performance of 3D printed concrete wall structures with cavities. J. Build. Eng. 2021, 41, 102431. [Google Scholar] [CrossRef]
  31. Alkhalidi, A.; Hatuqay, D. Energy efficient 3D printed buildings: Material and techniques selection worldwide study. J. Build. Eng. 2020, 30, 101286. [Google Scholar] [CrossRef]
  32. He, Y.; Zhang, Y.; Zhang, C.; Zhou, H. Energy-saving potential of 3D printed concrete building with integrated living wall. Energy Build. 2020, 222, 110110. [Google Scholar] [CrossRef]
  33. Craveiro, F.; Bartolo, H.; Gale, A.; Duarte, J.; Bartolo, P. A design tool for resource-efficient fabrication of 3d-graded structural building components using additive manufacturing. Autom. Constr. 2017, 82, 75–83. [Google Scholar] [CrossRef] [Green Version]
  34. ABAQUS. Hibbitt; Karlsson & Sorensen, Inc.: Pawtucket, RI, USA, 2021. [Google Scholar]
Figure 1. Examples of 3DPC wall panels with different cross-sectional arrangements: (a) triangular-shaped [25]; (b) lattice-shaped 3DPC wall by ETESIAS [26]; (c) sinusoidal-shaped 3DPC wall by Gosselin et al. [27]; (d) sinusoidal shaped, from the world’s largest 3DPC building in Dubai [28].
Figure 1. Examples of 3DPC wall panels with different cross-sectional arrangements: (a) triangular-shaped [25]; (b) lattice-shaped 3DPC wall by ETESIAS [26]; (c) sinusoidal-shaped 3DPC wall by Gosselin et al. [27]; (d) sinusoidal shaped, from the world’s largest 3DPC building in Dubai [28].
Buildings 11 00432 g001
Figure 2. The different 3DPC cavity wall configurations studied by Wang et al. [24]: (a) cellular topology; (b) triangular topology; (c) truss topology; (d) lattice topology.
Figure 2. The different 3DPC cavity wall configurations studied by Wang et al. [24]: (a) cellular topology; (b) triangular topology; (c) truss topology; (d) lattice topology.
Buildings 11 00432 g002
Figure 3. (a) Geometry and boundary conditions; (b) tie constraints; (c) meshing.
Figure 3. (a) Geometry and boundary conditions; (b) tie constraints; (c) meshing.
Buildings 11 00432 g003
Figure 4. Wall configurations proposed by Alkhalidi and Hatuqay [31]: (a) single row, 10 cm (W1); (b) single row, 15 cm (W2); (c) double row, 10 cm (W3); (d) double row, 15 cm (W4); (e) triple row, 10 cm (W5).
Figure 4. Wall configurations proposed by Alkhalidi and Hatuqay [31]: (a) single row, 10 cm (W1); (b) single row, 15 cm (W2); (c) double row, 10 cm (W3); (d) double row, 15 cm (W4); (e) triple row, 10 cm (W5).
Buildings 11 00432 g004
Figure 5. (a) Concrete Mix 1 U-value comparison; (b) concrete Mix 2 U-value comparison; (c) concrete Mix 3 U-value comparison.
Figure 5. (a) Concrete Mix 1 U-value comparison; (b) concrete Mix 2 U-value comparison; (c) concrete Mix 3 U-value comparison.
Buildings 11 00432 g005aBuildings 11 00432 g005b
Figure 6. The U-value results obtained for different wall configurations with different wall thickness.
Figure 6. The U-value results obtained for different wall configurations with different wall thickness.
Buildings 11 00432 g006
Figure 7. The U-value results obtained for 100 mm wall configurations with and without cavity insulation.
Figure 7. The U-value results obtained for 100 mm wall configurations with and without cavity insulation.
Buildings 11 00432 g007
Figure 8. The U-value results obtained for 200 mm wall configurations with and without cavity insulation.
Figure 8. The U-value results obtained for 200 mm wall configurations with and without cavity insulation.
Buildings 11 00432 g008
Figure 9. The U-value results obtained for 100 mm and 200 mm wall configurations with and without cavity insulation.
Figure 9. The U-value results obtained for 100 mm and 200 mm wall configurations with and without cavity insulation.
Buildings 11 00432 g009
Figure 10. The U-value variation with cavity area.
Figure 10. The U-value variation with cavity area.
Buildings 11 00432 g010
Figure 11. Heat-flux colour distribution along the 100 mm wall configurations.
Figure 11. Heat-flux colour distribution along the 100 mm wall configurations.
Buildings 11 00432 g011aBuildings 11 00432 g011bBuildings 11 00432 g011c
Figure 12. Heat-flux colour distribution along the 200 mm wall configurations.
Figure 12. Heat-flux colour distribution along the 200 mm wall configurations.
Buildings 11 00432 g012aBuildings 11 00432 g012bBuildings 11 00432 g012c
Table 1. Properties of the concrete mix [31].
Table 1. Properties of the concrete mix [31].
MixDensity (kg/m3)Thermal Conductivity (W/m·K)Specific Heat (J/g·K)Emissivity
Mix 112540.3670.8030.558
Mix 29860.3381.1270.583
Mix 315220.20.730.94
Table 2. Thermophysical properties of the cavity insulation [31].
Table 2. Thermophysical properties of the cavity insulation [31].
Cavity FillingDensity (kg/m3)Thermal Conductivity (W/m·K)Specific Heat (J/g·K)Viscosity (kg/m·s)
Air cavityIdeal gas0.02421.006431.7894 × 10−5
E-PLA300.031.483-
Table 3. Outline of the parametric study.
Table 3. Outline of the parametric study.
Wall ThicknessWall ConfigurationInsulation TypeNumber of Models
100 mm
200 mm
C1Air cavity
E-PLA insulation
4
C24
C34
C44
C54
C64
C74
C84
Total 32
Table 4. Different cross-sectioned 3DPC wall configurations.
Table 4. Different cross-sectioned 3DPC wall configurations.
Wall
Configuration (1 m Length)
100 mm (12 mm Layer)200 mm (25 mm Layer)
C1 Buildings 11 00432 i001 Buildings 11 00432 i002
C2 Buildings 11 00432 i003 Buildings 11 00432 i004
C3 Buildings 11 00432 i005 Buildings 11 00432 i006
C4 Buildings 11 00432 i007 Buildings 11 00432 i008
C5 Buildings 11 00432 i009 Buildings 11 00432 i010
C6 Buildings 11 00432 i011 Buildings 11 00432 i012
C7 Buildings 11 00432 i013 Buildings 11 00432 i014
C8 Buildings 11 00432 i015 Buildings 11 00432 i016
Table 5. The U-values derived from the FE analysis.
Table 5. The U-values derived from the FE analysis.
Wall ConfigurationCavity Area (mm2)Concrete Area (mm2)U-Values
Cavity WallE-PLA Insulated Wall
C110052,51947,4812.680.87
C210064,14435,8563.160.65
C310057,17442,8262.790.64
C410023,92376,0771.851.42
C510023,92376,0771.851.42
C610045,56854,4321.890.96
C710037,73662,2642.090.68
C810037,73662,2642.090.69
C120099,330100,6701.740.45
C2200126,22573,7751.260.50
C3200106,85593,1451.710.49
C420043,477156,5231.010.73
C520043,477156,5231.010.72
C620087,500112,5002.170.34
C720072,721127,2791.010.49
C820072,721127,2791.010.50
Table 6. The U-value reduction percentages.
Table 6. The U-value reduction percentages.
Wall ArrangementU-Value Reduction Percentage for Double Rows (%)
100 mm Wall200 mm Wall
Triangular30.7142.10
Lattice40.13−42.03
Sinusoid25.0240.72
Table 7. The U-value reduction percentages (%) with insulation.
Table 7. The U-value reduction percentages (%) with insulation.
Wall ConfigurationU-Value Reduction Percentage (%)Wall ConfigurationU-Value Reduction Percentage (%)
C110067.67C120074.20
C210079.59C220060.50
C310077.09C320071.38
C410023.62C420027.64
C510023.61C520028.23
C610049.22C620084.29
C710067.51C720051.51
C810066.88C820050.49
Table 8. Comparison of U-values.
Table 8. Comparison of U-values.
WallCavity Area (m2)Concrete Area (m2)Avg Cavity Thickness (m)Avg Concrete Thickness (m)λc (W/m2·K)λs (W/m2·K)R ValueU Value Equation (5)U Value FEMEquation/FEM
C110052519474810.050.050.360.20.392.602.680.97
C210064144358560.060.040.420.20.333.023.160.96
C310057174428260.060.040.360.20.382.672.790.96
C410023923760770.020.080.140.20.551.831.850.99
C510023923760770.020.080.140.20.551.831.850.99
C610045568544320.050.050.180.20.531.891.891.00
C710037736622640.040.060.220.20.482.082.090.99
C810037736622640.040.060.220.20.482.082.090.99
Mean1.00
COV0.02
Note: λc: thermal conductivity of cavity; λs: thermal conductivity of solid; AT; total area of the wall section; Ac: cavity area of the wall section; Lw: length of the wall section.
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Suntharalingam, T.; Upasiri, I.; Gatheeshgar, P.; Poologanathan, K.; Nagaratnam, B.; Santos, P.; Rajanayagam, H. Energy Performance of 3D-Printed Concrete Walls: A Numerical Study. Buildings 2021, 11, 432. https://0-doi-org.brum.beds.ac.uk/10.3390/buildings11100432

AMA Style

Suntharalingam T, Upasiri I, Gatheeshgar P, Poologanathan K, Nagaratnam B, Santos P, Rajanayagam H. Energy Performance of 3D-Printed Concrete Walls: A Numerical Study. Buildings. 2021; 11(10):432. https://0-doi-org.brum.beds.ac.uk/10.3390/buildings11100432

Chicago/Turabian Style

Suntharalingam, Thadshajini, Irindu Upasiri, Perampalam Gatheeshgar, Keerthan Poologanathan, Brabha Nagaratnam, Paulo Santos, and Heshachanaa Rajanayagam. 2021. "Energy Performance of 3D-Printed Concrete Walls: A Numerical Study" Buildings 11, no. 10: 432. https://0-doi-org.brum.beds.ac.uk/10.3390/buildings11100432

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop