Article

Thermohydraulic Performance and Entropy Generation of a Triple-Pass Solar Air Heater with Three Inlets

1
Faculty of Heat and Refrigeration Engineering, Industrial University of Ho Chi Minh City (IUH), 12 Nguyen Van Bao, Go Vap District, Ho Chi Minh City 700000, Vietnam
2
Faculty of Mechanical Engineering, Ho Chi Minh City University of Technology (HCMUT), 268 Ly Thuong Kiet, District 10, Ho Chi Minh City 700000, Vietnam
3
Vietnam National University, Linh Trung Ward, Thu Duc District, Ho Chi Minh City 700000, Vietnam
*
Author to whom correspondence should be addressed.
Submission received: 4 September 2021 / Revised: 29 September 2021 / Accepted: 4 October 2021 / Published: 7 October 2021
(This article belongs to the Special Issue Fluid Flow and Heat Transfer Analysis in Industrial Applications)

Abstract

:
In this paper, a triple-pass solar air heater with three inlets is analytically investigated. The effects of airflow ratios of the second and third passes (ranging from 0 to 0.4), and the Reynolds number of the third pass (ranging from 8000 to 18,000) on the thermohydraulic efficiency and entropy generation are assessed. An absorber plate equipped with rectangular fins on both sides is used to enhance heat transfer. The air temperature change in the passes is represented by ordinary differential equations and solved by numerical integration. The results demonstrate that the effect of the third pass airflow ratio on the thermohydraulic efficiency and entropy generation is more significant than that of the second pass airflow ratio. The difference in air temperature through the collector shows an insignificant reduction, but the air pressure loss is only 50% compared with that of a traditional triple-pass solar air heater. Increasing the air flow ratios dramatically reduces entropy generation. Multi-objective optimization found a Reynolds number of 11,156 for both the airflow ratio of the second pass of 0.258 and airflow ratio of the third pass of 0.036 to be the an optimal value to achieve maximum thermohydraulic efficiency and minimum entropy generation.

1. Introduction

Hot air is an essential source of thermal energy for industrial fields such as regarding drying, pre-heating of bottles, textile production processes, painting processes, and conditioning tobacco. For moderate-temperature heating, a solar air heater (SAH) can be employed, which reduces fossil fuel energy consumption [1]. SAHs are the simplest energy conversion devices, as they can be made from locally available materials. However, SAHs reveal some limitations that arise from the heat transfer fluid of air, which cannot be stored as hot water can, and the low convection heat transfer coefficient of air. Heat transfer improvement between the airflow and absorption plate of a SAH is a topic of constant interest to researchers. Inserts including rib roughness, fins, porous media, or baffles in the SAH duct have led to increases in the heat transfer rate due to the elimination of the laminar sub-layer close to the absorber plate and airflow reconfiguration [2,3]. The small convection heat transfer coefficient of the air leads to a high absorber plate temperature, resulting in a large top heat loss of the SAH. To reduce this heat loss, airflow with multiple passes is structured such that the air receives heat from both sides of the absorber plate, glass, and back plate. [4,5]. Tuncer et al. [6] used triple and quadruple-pass SAHs to dry food. They reported that pressure losses of 3.8 and 4.5 Pa were obtained for triple and quadruple-pass SAHs, respectively. In addition, air temperature increases of 18.2 and 20.1 °C were observed in the triple and quadruple-pass SAHs, respectively. Khanlari et al. [7] dried municipal sewage sludge using triple and quadruple-pass SAHs. A V-groove absorber plate was designed to enhance heat transfer. Their experimental results proved that the collector efficiency can be up to 81.7%. Potato drying using a triple-pass SAH has been experimentally examined by Kesavan et al. [8]. A wire mesh in the second pass and sand as a thermal storage medium were adopted in order to increase the heat transfer rate and extend the drying time. The highest thermal and exergy efficiencies of 66% and 87%, respectively, were deduced. Sopian et al. [9] discussed a double-pass solar collector with porous media in the second pass. They confirmed that the collector had a higher thermal efficiency compared to that of a single-pass SAH.
Another modification to multi-pass SAHs is the adjustment of the air flow in each channel by recycling flow or adding air inlets. This correction can improve collector performance, as the multi-pass air collector has a large pressure loss and the temperature difference between the fluid and the surface in each channel differs. Table 1 summarizes studies on the flow patterns changed in the multi-pass SAHs. Ho et al. [10] explored a double-pass SAH with recycled flow. Wire mesh, as a heat transfer enhancement media, was inserted in the channel between the absorber plate and back plate. They reported an optimal recycle ratio of 1.0 to obtain the highest collector efficiency improvement. Yeh and Ho [11] divided the space between the absorber plate and back plate into two air channels. Longitudinal fins were attached to the absorber plate in order to intensify the heat exchange. They concluded that the collector efficiency can be improved through an increase in the reflux ratio. Singh and Dhiman [12] added wire mesh packing in the main air channel between a glass cover and absorber plate. The recycle ratio of 1.8 yielded the largest thermohydraulic efficiency. Ho et al. [13] utilized corrugated absorber and back plates to improve heat transfer in a double-pass SAH with recycled flow. It was shown that the thermal performance improved with an increasing recycle ratio and decreasing air flow rate. The optimum recycle ratio of 0.5 was found considering the trade-off of heat transfer improvement and pressure loss penalty. Abo-Elfadl et al. [14] recently added an air inlet port in the second pass of a double-pass SAH. The absorber plate was equipped with pin fins for heat transfer augmentation. They confirmed that 66.7% of the air supply at the port led to the highest energy and exergy efficiencies. More recently, Ahmadkhani et al. [15] investigated two flow configurations, including recycled flow to the back plate or upper glass cover. A packed bed matrix was utilized in the main air channel to perform the parametric study. It was identified that the recycled flow to the back plate led to a higher air temperature rise.
The above literature review indicates that multiple passes and various air flows within the passes can improve the thermohydraulic performance of an SAH. However, a study for triple-pass SAHs with air flow modification was not found. Furthermore, studies focused on the parameters related to the second law of thermodynamics are lacking. In this study, a triple-pass SAH with three inlets each at an air pass is investigated. The main aim of the present study was to determine the flow rate of each pass such that the collector efficiency can be augmented and the entropy generation lowered.

2. Model Description

The schematic diagram of a three-inlet triple-pass air collector is shown in Figure 1. In this study, the collector dimensions are fixed, including the collector length L, width W, and depth of an air channel D. The collector includes two glass covers, one absorber plate, and one back plate. The air travels through the surfaces in turn, forming three passes. Each pass has an air inlet with ambient temperature Ta, as shown in the figure. The air flow through the third pass is the total flow, with the mass flow rate m ˙ . Let y and z be the additional air fractions supplied to passes 2 and 3, respectively. The air fraction through the first pass is (1 − yz). The two sides of the absorber plate was equipped with longitudinal fins in order to enhance the heat transfer for the plate. The mathematical model is established with the following assumptions:
-
The flow in a channel is considered one-dimensional in the x-direction.
-
The flow is steady and the air fluid is incompressible.
-
The thermophysical properties of the air and the SAH are temperature-independent; and
-
The bottom plate and the edges of the SAH are perfectly insulated from the surrounding environment.
The heat balance equation for the glass, plates, and air in the three channels is as follows:
-
Glass 1: Solar irradiation absorbed by the glass balances the heat exchanged by convection and radiation from the top and bottom sides of the glass [4,16]:
I α g 1 + h w ( T a T g 1 ) + h r , a ( T s k y T g 1 ) + h r , g 1 , g 2 ( T g 2 T g 1 ) + h f 1 , g 1 ( T f 1 T g 1 ) = 0 ,
where the sky temperature is calculated by T s k y = 0.0552 T a 1.5 .
-
The heat gain of first pass air in an infinitesimal change (dx) is equal to the heat exchange by convection with glasses 1 and 2 as:
( 1 y z ) m ˙ c p d T f 1 = [ W h f 1 , g 1 ( T g 1 T f 1 ) + W h f 1 , g 2 ( T g 2 T f 1 ) ] d x .
Therefore, the variation in the first pass air temperature along the x-direction due to the convection heat transfer of the air with the two glasses is expressed as follows:
d T f 1 d x = W h f 1 , g 1 ( T g 1 T f 1 ) + W h f 1 , g 2 ( T g 2 T f 1 ) ( 1 y z ) m ˙ c p .
-
Similarly, for glass 2:
I τ g 1 α g 2 + h f 1 , g 2 ( T f 1 T g 2 ) + h f 2 , g 2 ( T f 2 T g 2 ) + h r , g 1 , g 2 ( T g 1 T g 2 ) + h r , g 2 , p 1 ( T p 1 T g 2 ) = 0 .
-
Similar to the change of the first pass air temperature, the air in the second pass exchanges heat with glass 2 and receives thermal energy by convection with the finned absorber plate. The convection heat transfer of the air with the fins and their prime surface is calculated through the temperature difference of the absorber plate (Tp) and the air (Tf2) with the fin efficiency. Hence, the change in the second pass air temperature can be written as:
d T f 2 d x = W h f 2 , g 2 ( T g 2 T f 2 ) + W h f 2 , p ϕ ( T p T f 2 ) ( 1 z ) m ˙ c p ,
where ϕ is the area-weighted fin efficiency.
-
The absorber plate can be expressed as:
I τ g 1 τ g 2 α p + h f 2 , p ϕ ( T f 2 T p ) + h r , g 2 , p ( T g 2 T p ) + h f 3 , p ϕ ( T f 3 T p 1 ) + h r , b , p ( T b T p ) = 0 .
-
The change in the third pass air temperature can be expressed as:
d T f 3 d x = W h f 3 , p ϕ ( T p T f 3 ) + W h f 3 , b ( T b T f 3 ) m ˙ c p .
-
The back plate-received radiation heat transfer from the absorber plate and transfer heat to the third pass air by convection is expressed as:
h f 3 , b ( T f 3 + T b ) + h r , b , p ( T b T p ) = 0 .
Boundary conditions for the ordinary differential Equations (2), (4) and (6) are as follows:
The temperature of the air entering the first pass (Tf1(x = 0)) is equal to the ambient temperature (Ta):
Tf1(x = 0) = Ta.
-
The air entering the second pass with a flow fraction (1 − z) is a mixture of the air exiting the first pass with the flow fraction (1 − yz) and the air from the second inlet with the flow fraction (y). The mixing temperature is calculated from the mass-weighted average as follows:
Tf2(x = L) = [(1 − yz)Tf1(x = L) + yTa]/(1 − z).
-
Similarly, the temperature boundary condition for the air entering the third pass can also be expressed as:
Tf3(x = 0) = (1 − z)Tf2(x = 0) + zTa.
The radiative heat transfer coefficient in the above system of equations can be evaluated through the following:
-
Radiation from glass 1 to the surroundings:
h r , a = σ ε g 1 ( T g 1 2 + T s k y 2 ) ( T g 1 + T s k y ) ;
-
Radiation of glasses:
h r , g 1 , g 2 = σ ( T g 1 2 + T g 2 2 ) T g 1 + T g 2 1 / ε g 1 + 1 / ε g 2 1 ;
-
Radiation of glass 1 and the absorber plate:
h r , g 2 , p = σ ( T g 2 2 + T p 2 ) T g 2 + T p 1 / ε g 2 + 1 / ε p 1 ;   and
-
Radiation of the absorber plate and back plate:
h r , b , p = σ ( T b 2 + T p 2 ) T b + T p 1 / ε b + 1 / ε p 1 .
The convective heat transfer coefficient of the air in the ducts can be estimated from the empirical correlation. The correlation was developed for the rectangular solar heater duct in the thermally developing flow [17] and has been adopted by many studies on solar air heater ducts [18,19,20].
h f 1 , g 1 = h f 1 , g 2 = 0.018 R e 1 0.8 P r 0.4 k / D e ,
h f 2 , g 2 = h f 2 , p = 0.018 R e 2 0.8 P r 0.4 k / D e ,
h f 3 , p = h f 3 , p = 0.018 R e 3 0.8 P r 0.4 k / D e ,
where Pr and De are the Prandtl number and hydraulic diameter of the air duct, respectively, and Re1, Re2, and Re3 are the respective Reynolds numbers in passes 1, 2, and 3. These quantities are defined by:
R e 1 = ρ D e V 1 / μ ,
R e 2 = ρ D e V 2 / μ ,
R e 3 = ρ D e V 3 / μ ,
P r = μ c p / k ,
D e = 4 W D 2 ( W + D ) .
The wind loss heat transfer coefficient for glass 1 can be determined using the McAdams formula [21]:
h w = 5.7 + 1.2 V w .
The area-weighted fin efficiency can be estimated as [11,18,19]:
ϕ = 1 + ( A f / A c ) η f ,
where Af is the total surface area of the fins and Ac is the collector surface area with A f = 2 n W f L and Ac = LW, in which n and Wf are the number of fins and fin height, respectively.
The fin efficiency is defined as:
η f = t a n h ( M W f ) M W f ,
where M = 2 h f 1 , g 1 k s t , in which t and ks are the fin thickness and thermal conductivity of the fin, respectively.
The air mass flow rate ( m ˙ ) and air velocity (V) have the following relations:
-
For the first pass,
( 1 y z ) m ˙ = W D ρ V 1 ;
-
for the second pass,
( 1 y ) m ˙ = W D ρ V 2 ;   and
-
for the third pass,
m ˙ = W D ρ V 3 .
The useful heat gain is determined from the air temperature difference of the collector as follows:
Q = m ˙ c p ( T o T a ) .
The air pumping power can be calculated by:
P f l o w = m ˙ Δ P ρ ,
where ΔP is the air pressure difference through the collector, which sums the pressure drops of passes, as expressed by:
Δ P = 2 ρ f 1 V 1 2 L D e + 2 ρ f 2 V 2 2 L D e + 2 ρ f 3 V 3 2 L D e .
The friction factor of each pass is given as [17,18]:
f 1 = 0.079 R e 1 0.25 ,
f 2 = 0.079 R e 2 0.25 ,   and
f 3 = 0.079 R e 3 0.25 .
Therefore, the thermohydraulic efficiency is defined as:
η e f f = Q P f l o w / C o L W I ,
where Co is the conversion factor of the mechanical work to heat (Co = 0.2) [4,22].
Entropy generation of a SAH exists as a result of irreversibility. The irreversibility may consist of the absorption of radiation by the absorber plate, heat transfer to the working air, heat loss to the environment, and frictional loss of the working air. The entropy generation can be determined using the entropy balance for a steady control volume without work transfer [23,24]:
S g e n = ( 1 / T a 1 / T s ) Q s + [ l n ( T o / T a ) T o / T a + 1 ] m ˙ c p m ˙ R l n ( P a P a + Δ P ) ,
where Ts is the solar temperature (Ts = 5777 K) and Qs is the solar energy absorbed by the absorber plate (Qs = I(τα)LW).
The parameters used as input for the mathematical model are reported in Table 2. Most of the parameters were obtained from the study of Ramani et al. [16] for the sake of validating numerical computation in the present study. The thermophysical parameters of air were estimated at ambient temperature. Temperature gradient equations—that is, Equations (3), (5) and (7)—can be solved by numerical integration in the form of Equation (28) [25]. The code for the solution of the governing equations was implemented in the software EES [26] using the built-in integral function. The details of the solution procedure are presented in the textbook of Nellis and Klein [27]. Figure 2 shows a comparison of the air temperature distribution in a double-pass solar air collector. There is good agreement between the results obtained in this study and the published results. Thus, the formulation of the governing equations and solution strategy can ensure accuracy of the results.
Δ T = 0 L d T f d x d x .
Table 3 presents the range of key parameters that were used to investigate the thermohydraulic performance and entropy generation in this study. It should be noted that the case with y = z = 0 is the traditional triple-pass collector. This case is considered as the base case for comparison with cases where y or z is greater than zero. For the multi-objective optimization of maximum thermohydraulic efficiency and minimum entropy generation, a genetic algorithm (GA) was adopted. The settings of the GA are provided in Table 4, which were partially adapted to our previous study [29]. The optimum curve can be displayed by means of a Pareto front [30]. To specify the ultimate optimal solution in terms of Pareto optimality, the TOPSIS (Technique for Order of Preference by Similarity to Ideal Solution) decision-making process was adopted. Another common decision-making technique is LINMAP (Linear Programming Technique for Multi-dimensional Analysis of Preference). The LINMAP method chooses the best solution by finding the shortest distance to the ideal point. The TOPSIS is attributed to the better method because the idea of this technique is to seek out the point that is nearest to the ideal point and the furthermost from the non-ideal point [31]. The lengths from a point to the ideal point (li+) and non-ideal point (li) are estimated as [32]:
l i + = ( S g e n S g e n , i d e a l ) 2 + ( η e f f η e f f , i d e a l ) 2 ,
l i = ( S g e n S g e n , n o n - i d e a l ) 2 + ( η e f f η e f f , n o n - i d e a l ) 2 .
To meet the condition of TOPSIS, the ultimate optimal solution has the biggest value of the ratio, as given by:
C l i = l i l i + l i + .

3. Results and Discussion

The influence of key parameters on the thermohydraulic efficiency, entropy generation, and the determination of optimal parameters is presented in this section. Figure 3, Figure 4, Figure 5, Figure 6, Figure 7 and Figure 8 show the influence of air flow ratios on the thermo-hydraulic parameters and entropy generation at Re3 = 10,000. The effect of air flow ratios on the temperature difference through the collector is presented in Figure 3. A general trend can be seen that as the ratio increases, the temperature difference decreases. In the base case (y = z = 0), the air temperature difference was the largest. This is because the reduced air flow in passes 1 or 2 decreased the convection heat exchange coefficient, thereby reducing the heat transfer capacity. It can be clearly seen, however, that the reduction of the temperature difference with the flow ratios was not significant. In the case where y = z = 0.4, the air temperature difference was about 0.15 K lower than that of the base case. This was due to the fact that radiant heat transfer existed in the multi-pass air collector. Figure 4 shows the average radiant heat transfer coefficients which were calculated from the average temperature of the surfaces. It is clear that as the Reynolds number increased, the radiant heat transfer coefficient decreased due to a decrease in the surface temperatures. However, at certain Reynolds numbers, all radiant heat transfer coefficients of the three-inlet SAH with airflow ratios of 0.4 were greater than those of the base case. This resulted in a negligible decrease in the air temperature difference with increasing airflow ratios. As the air flow decreased, the temperature of the heat exchanger surfaces increased, thereby increasing the temperature difference between the fluid and the heat transfer surface. The heat transfer rate was proportional to the temperature difference. The temperature distributions of the air flows and heat transfer surfaces are depicted in Figure 5 with respect to the extremes of the airflow ratios (i.e., 0 and 0.4).
The air temperature increased gradually through the passes. In the case of three inlets (Figure 5b), air temperatures entering the second and third passes were reduced compared to the air temperatures exiting the first and second passes, respectively. The temperatures in the first and second passes were reduced due to the fact that cool ambient air entered the collector from the additional inlets with the airflows of y m ˙ and z m ˙ , respectively. It is clear that when decreasing the air flow rate of passes 1 and 2, the air temperature difference at these passes increases. The third pass had the same flow rate for both cases in Figure 5. However, the air temperature difference of the third pass in the three-inlet collector was much larger than that of the traditional triple-pass SAH: about 6 K vs. 4 K. This is because the average temperature of the absorber plate of the base case was about 41 °C, while that in the case where y = z = 0.4 was about 43 °C. In the base case (Figure 5a), the airflow in the first pass received heat mainly from glass 2. The difference in air temperature through the second pass was the largest, as this was the main pass (i.e., the air exchanged heat with the absorber plate). Hence, the temperature cross occurred between the second pass air temperature (Tf2) and temperature of glass 2 (Tg2). The absorber plate temperature profile was in line with the second pass air temperature. In the case y = z = 0.4 (Figure 5b), the first pass air received heat from the upper glass until x = 0.5 m, as the lower air flow led to higher glass temperatures. The absorber plate temperature (Tp) reached its maximum in the middle of the collector (x = 1.1 m), as the heat exchange occurring at the second and third passes was almost the same. However, the direction of the temperature rise of these two passes was opposite, such that the absorber plate temperature reached its maximum in the middle of the collector.
The hydraulic loss with flow ratios is shown in Figure 6. It can be clearly observed that the air pressure difference decreased notably with increasing flow ratios: 25.5 Pa in the base case and 13 Pa at y = z = 0.4 (i.e., pressure drop by a half). Figure 7 illustrates the variations of useful heat gain and pumping power, as assessed by thermohydraulic efficiency, with air flow ratios. Taking the aforementioned discussions into account, we determined that the efficiency can reach a maximum at a certain airflow ratio. Greater efficiencies were achieved at flow ratios less than 0.1. This is because the performance of an SAH is dominated by heat transfer compared to pumping power. The thermohydraulic efficiency reached a maximum of 64.65% at z = 0 and y = 0.2. At z = 0.4, the efficiency dropped from 64.42 to 64.08% when increasing y from 0 to 0.4. At y = 0.4, the efficiency decreased from 64.62 to 64.08% as z increased from 0 to 0.4. In other words, the thermohydraulic parameters were affected more strongly by the change of feed air into the third pass. Figure 8 shows the entropy generation with flow ratios. We observed that the entropy generation decreases with the increase of airflow ratios. This behavior results from a change in the airflow ratio, which had little effect on the outlet temperature but greatly reduced the pressure loss. The effect of the irreversibility due to the frictional loss can be expressed by the last term of Equation (27). Entropy generation decreased from 2.442 W/K to 2.384 W/K when increasing flow ratios from 0 to 0.4.
The impacts of the Reynolds number in the third pass (Re3) and the airflow ratios are shown in Figure 9, Figure 10, Figure 11 and Figure 12. As the Reynolds number increased, both heat transfer and pressure loss increased. The convection heat transfer coefficient was proportional to the 0.8 power of the Reynolds number (Equation (14)) and the air pumping power was proportional to the 2.75 power of the Reynolds number (Equations (23)–(25)). Hence, the efficiency peaked at some Reynolds number when the ratios were fixed, as seen in Figure 9 and Figure 11. It can be inferred from Figure 9 that the maximum efficiency at each z-value was roughly the same. However, when z was larger, the optimum Re3 was also greater. At z = 0, the optimal Re number was around 10,000, while the optimal Re number was around 13,000 at z = 0.4. This is a promising outcome in terms of increasing the air flow through the triple-pass collector with additional inlets. In addition, when Re3 > 11,000, the base case performance was minimal. Entropy generation increased with an increasing Reynolds number and with decreasing flow ratios, as can be observed from Figure 10 and Figure 12. The increase of the entropy generation with the Reynolds number was mainly due to increased pressure loss penalty (ΔP). It can be noticed that the effect of z on the efficiency and entropy generation was more pronounced than that of y, as the third pass was the main heat exchange channel and the pressure loss was the largest for the triple-pass SAH with three inlets. From Figure 9 and Figure 11, it can be concluded that a three-inlet air collector should be used when the Reynolds number is greater than 11,000 in terms of the thermohydraulic performance.
From the above parametric study, it can be seen that the Reynolds number and airflow ratios had opposite effects on collector efficiency and entropy generation. The maximum efficiency was achieved at a certain Reynolds number and at certain airflow ratios in the surveyed range. Meanwhile, entropy generation increased with the increase of Re and decrease of flow ratios. Therefore, to assign optimal values of independent parameters, a Pareto front was constructed, as shown in Figure 13. The Pareto front curve was established using the genetic algorithm with the settings shown in Table 4. The curve was a series of optimal solutions that yielded a large efficiency and small entropy generation. Ideal and non-ideal points located at the vertices of the rectangle formed by the Pareto curve were found. To determine the final solution, the TOPSIS decision-making technique was applied, which found Sgen = 2.4691 W/K and ηeff = 65.38%, as shown in the graph. This is the point that was closest to the ideal point (bottom-right corner) and furthest from the non-ideal point (top-left corner). The optimal parameters at the selected point were found to be Re3 = 11,156, y = 0.258, and z = 0.036. In addition, Figure 13 also shows the maximum efficiency value corresponding to the maximum entropy generation and vice versa.

4. Conclusions

A one-dimensional analytical model was formed to evaluate the temperature distribution in a three-inlet triple-pass solar air heater. Thermohydraulic efficiency and entropy generation served as the criteria to estimate its performance when changing the Reynolds number of the air in the third pass and in the airflow ratio of the inlets. The thermohydraulic performance and entropy generation were significantly improved by adding inlets when the collector operated with a high airflow. The main findings of the present research study are as follows:
  • The air temperature difference showed little change with the airflow ratios. However, the pressure loss of the three-inlet triple-pass SAH was reduced to half of that of the traditional triple-pass SAH.
  • Thermohydraulic efficiency reached high values when the airflow ratios were less than 0.1.
  • Increasing the airflow ratio increased the optimal Reynolds number for maximum thermohydraulic efficiency.
  • When the Reynolds number was greater than 11,000, the performance of the three-inlet triple-pass SAH was greater than that of the traditional triple-pass SAH.
  • Increasing the Reynolds number and decreasing the airflow ratios increased entropy generation.
  • The influence of the third pass airflow ratio on the thermal–hydraulic parameters and entropy generation was more pronounced than that of the airflow ratio of the second pass.
  • Re3 = 11,156, y = 0.258, and z = 0.036 are the optimal values for maximum thermohydraulic efficiency and minimum entropy generation.

Author Contributions

Conceptualization, N.M.P.; investigation, N.T.T., N.V.H. and N.M.P.; methodology, N.M.P.; software, N.T.T. and N.M.P.; supervision, N.M.P.; validation, N.T.T.; visualization, N.V.H.; writing—original draft preparation, N.T.T. All authors have read and agreed to the published version of the manuscript.

Funding

Not applicable.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

Not applicable.

Acknowledgments

We would like to thank the Industrial University of Ho Chi Minh City (IUH) and Ho Chi Minh City University of Technology (HCMUT), VNU-HCM, for their time, support, and facilities for this study.

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

Acarea of absorber plate (m2)
cpspecific heat at a constant pressure (Jkg−1K−1)
Dchannel depth (m)
Dehydraulic diameter (m)
ffriction factor
hheat transfer coefficient (Wm−2K−1)
Isolar radiation (W/m2)
kthermal conductivity (Wm−1K−1)
Lcollector length (m)
m ˙ air mass flow rate (kg/s)
nnumber of fins
Ppressure (Pa)
PrPrandtl number
Qheat transfer rate (W)
ReReynolds number
Sgenentropy generation (W/K)
tfin thickness (m)
Ttemperature (K)
Vvelocity (m/s)
Wcollector width (m)
Wffin height (m)
xcoordinator (m)
yairflow ratio of the second pass, 0 ≤ y < 1
zairflow ratio of the third pass, 0 ≤ z < 1
Greek symbols
αabsorptivity
Δdifference
εemissivity
ηefficiency
μdynamic viscosity (Pa.s)
ϕarea-weighted fin efficiency
ρair density (kg/m3)
σStefan constant
τtransmissivity
Subscripts
aambient
bback plate
cconvection
Effthermohydraulic
ffluid (Air), fin
gglass cover
ooutlet
pabsorber plate
rradiation
ssun
wwind

References

  1. Farjana, S.H.; Huda, N.; Mahmud, M.A.P.; Saidur, R. Solar process heat in industrial systems—A global review. Renew. Sust. Energ. Rev. 2018, 82, 2270–2286. [Google Scholar] [CrossRef] [Green Version]
  2. Phu, N.M.; Luan, N.T. A review of energy and exergy analyses of a roughened solar air heater. J. Adv. Res. Fluid Mech. Therm. Sci. 2021, 77, 160–175. [Google Scholar]
  3. Thao, P.B.; Truyen, D.C.; Phu, N.M. CFD Analysis and Taguchi-Based Optimization of the Thermohydraulic Performance of a Solar Air Heater Duct Baffled on a Back Plate. Appl. Sci. 2021, 11, 4645. [Google Scholar] [CrossRef]
  4. Nguyen Thanh, L.; Nguyen Minh, P. First and Second Law Evaluation of Multipass Flat-Plate Solar Air Collector and Optimization Using Preference Selection Index Method. Math. Probl. Eng. 2021, 2021, 5563882. [Google Scholar]
  5. Chamoli, S.; Chauhan, R.; Thakur, N.; Saini, J. A review of the performance of double pass solar air heater. Renew. Sust. Energ. Rev. 2012, 16, 481–492. [Google Scholar] [CrossRef]
  6. Tuncer, A.D.; Sözen, A.; Khanlari, A.; Amini, A.; Şirin, C. Thermal performance analysis of a quadruple-pass solar air collector assisted pilot-scale greenhouse dryer. Sol. Energy 2020, 203, 304–316. [Google Scholar] [CrossRef]
  7. Khanlari, A.; Sözen, A.; Afshari, F.; Şirin, C.; Tuncer, A.D.; Gungor, A. Drying municipal sewage sludge with v-groove triple-pass and quadruple-pass solar air heaters along with testing of a solar absorber drying chamber. Sci. Total Environ. 2020, 709, 136198. [Google Scholar] [CrossRef]
  8. Kesavan, S.; Arjunan, T.; Vijayan, S. Thermodynamic analysis of a triple-pass solar dryer for drying potato slices. J. Therm. Anal. Calorim. 2019, 136, 159–171. [Google Scholar] [CrossRef]
  9. Sopian, K.; Alghoul, M.; Alfegi, E.M.; Sulaiman, M.; Musa, E. Evaluation of thermal efficiency of double-pass solar collector with porous–nonporous media. Renew. Energy 2009, 34, 640–645. [Google Scholar] [CrossRef]
  10. Ho, C.-D.; Lin, C.-S.; Chuang, Y.-C.; Chao, C.-C. Performance improvement of wire mesh packed double-pass solar air heaters with external recycle. Renew. Energy 2013, 57, 479–489. [Google Scholar] [CrossRef]
  11. Yeh, H.-M.; Ho, C.-D. Collector efficiency in downward-type internal-recycle solar air heaters with attached fins. Energies 2013, 6, 5130–5144. [Google Scholar] [CrossRef]
  12. Singh, S.; Dhiman, P. Analytical and experimental investigations of packed bed solar air heaters under the collective effect of recycle ratio and fractional mass flow rate. J. Energy Storage 2018, 16, 167–186. [Google Scholar] [CrossRef]
  13. Ho, C.-D.; Chang, H.; Hsiao, C.-F.; Huang, C.-C. Device performance improvement of recycling double-pass cross-corrugated solar air collectors. Energies 2018, 11, 338. [Google Scholar] [CrossRef] [Green Version]
  14. Abo-Elfadl, S.; Yousef, M.S.; Hassan, H. Assessment of double-pass pin finned solar air heater at different air mass ratios via energy, exergy, economic, and environmental (4E) approaches. Environ. Sci. Pollut. Res. 2021, 28, 13776–13789. [Google Scholar] [CrossRef]
  15. Ahmadkhani, A.; Sadeghi, G.; Safarzadeh, H. An in depth evaluation of matrix, external upstream and downstream recycles on a double pass flat plate solar air heater efficacy. Therm. Sci. Eng. Prog. 2021, 21, 100789. [Google Scholar] [CrossRef]
  16. Ramani, B.; Gupta, A.; Kumar, R. Performance of a double pass solar air collector. Sol. Energy 2010, 84, 1929–1937. [Google Scholar] [CrossRef]
  17. Tan, H.M.; Charters, W.W.S. Effect of thermal entrance region on turbulent forced-convective heat transfer for an asymmetrically heated rectangular duct with uniform heat flux. Sol. Energy 1969, 12, 513–516. [Google Scholar] [CrossRef]
  18. Sahu, M.K.; Sharma, M.; Matheswaran, M.; Maitra, K. On the use of longitudinal fins to enhance the performance in rectangular duct of solar air heaters—A review. J. Sol. Energy Eng. 2019, 141, 030802. [Google Scholar] [CrossRef]
  19. Velmurugan, P.; Kalaivanan, R. Thermal performance studies on multi-pass flat-plate solar air heater with longitudinal fins: An analytical approach. Arab. J. Sci. Eng. 2015, 40, 1141–1150. [Google Scholar] [CrossRef]
  20. Naphon, P. On the performance and entropy generation of the double-pass solar air heater with longitudinal fins. Renew. Energy 2005, 30, 1345–1357. [Google Scholar] [CrossRef]
  21. Phu, N.M.; Van Hap, N. Performance Evaluation of a Solar Air Heater Roughened with Conic-Curve Profile Ribs Based on Efficiencies and Entropy Generation. Arab. J. Sci. Eng. 2020, 45, 9023–9035. [Google Scholar] [CrossRef]
  22. Phu, N.M.; Bao, T.T.; Hung, H.N.; Tu, N.T.; Van Hap, N. Analytical predictions of exergoeconomic performance of a solar air heater with surface roughness of metal waste. J. Therm. Anal. Calorim. 2021, 144, 1727–1740. [Google Scholar] [CrossRef]
  23. Fudholi, A.; Sopian, K. A review of solar air flat plate collector for drying application. Renew. Sust. Energ. Rev. 2019, 102, 333–345. [Google Scholar] [CrossRef]
  24. Muñoz, M.; Roa, M.; Correa, R. Entropy generation analysis for the design of a flat plate solar collector with fins. Dyna 2020, 87, 199–208. [Google Scholar] [CrossRef] [Green Version]
  25. Phu, N.M.; Lee, G.S. Characteristics of pressure and force considering friction in a closed cylinder with a holed piston. J. Mech. Sci. Technol. 2014, 28, 2409–2415. [Google Scholar] [CrossRef]
  26. Klein, S.A. Engineering Equation Solver (EES); F-Chart Software: London, UK, 2013. [Google Scholar]
  27. Nellis, G.; Klein, S. Heat Transfer; Cambridge University Press: New York, NY, USA, 2009; pp. 317–348. [Google Scholar]
  28. Abuşka, M.; Şevik, S. Energy, exergy, economic and environmental (4E) analyses of flat-plate and V-groove solar air collectors based on aluminium and copper. Sol. Energy 2017, 158, 259–277. [Google Scholar] [CrossRef]
  29. Thao, P.B.; Phu, N.M.; Truyen, D.C. Comparative Study and Optimization of CO2 Capture and Storage in LNG-fired Power Plant. J. Adv. Res. Fluid Mech. Therm. Sci. 2020, 72, 55–66. [Google Scholar]
  30. Zhou, T.; Nguyen, V.H.; Lee, G.S. Design optimization of heat exchangers for solar-heating ocean thermal energy conversion (SH-OTEC) using high-performance commercial tubes. Trans. Korean Soc. Mech. Eng. B 2016, 40, 557–567. [Google Scholar] [CrossRef] [Green Version]
  31. Alhamid, M.I.; Aisyah, N. Exergetic-Economic analysis and optimization of solar assisted heat pump using Multi-objective Genetic Algorithm. IOP Conf. Ser. Earth Environ. Sci. 2018, 105, 012064. [Google Scholar]
  32. Tuyen, V.; Van Hap, N.; Phu, N.M. Thermal-hydraulic characteristics and optimization of a liquid-to-suction triple-tube heat exchanger. Case Stud. Therm. Eng. 2020, 19, 100635. [Google Scholar] [CrossRef]
  33. Imran, M.; Pambudi, N.A.; Farooq, M. Thermal and hydraulic optimization of plate heat exchanger using multi objective genetic algorithm. Case Stud. Therm. Eng. 2017, 10, 570–578. [Google Scholar] [CrossRef]
Figure 1. Triple-pass solar air heater with three inlets and notation.
Figure 1. Triple-pass solar air heater with three inlets and notation.
Energies 14 06399 g001
Figure 2. Validation of local air temperatures with the published data [16].
Figure 2. Validation of local air temperatures with the published data [16].
Energies 14 06399 g002
Figure 3. Effect of airflow ratios on temperature increase.
Figure 3. Effect of airflow ratios on temperature increase.
Energies 14 06399 g003
Figure 4. Comparison of the mean radiation heat transfer coefficient for the base case and the case with y = z = 0.4.
Figure 4. Comparison of the mean radiation heat transfer coefficient for the base case and the case with y = z = 0.4.
Energies 14 06399 g004
Figure 5. Local temperature of airflow in three passes, i.e., glass covers, absorber plate, and back plate at Re3 = 10,000: (a) y = z = 0 (base case) and (b) y = z = 0.4.
Figure 5. Local temperature of airflow in three passes, i.e., glass covers, absorber plate, and back plate at Re3 = 10,000: (a) y = z = 0 (base case) and (b) y = z = 0.4.
Energies 14 06399 g005
Figure 6. Effect of airflow ratios on pressure difference.
Figure 6. Effect of airflow ratios on pressure difference.
Energies 14 06399 g006
Figure 7. Effect of airflow ratios on thermohydraulic efficiency.
Figure 7. Effect of airflow ratios on thermohydraulic efficiency.
Energies 14 06399 g007
Figure 8. Effect of airflow ratios on entropy generation.
Figure 8. Effect of airflow ratios on entropy generation.
Energies 14 06399 g008
Figure 9. Effect of airflow ratio z and Reynolds number on thermohydraulic efficiency.
Figure 9. Effect of airflow ratio z and Reynolds number on thermohydraulic efficiency.
Energies 14 06399 g009
Figure 10. Effect of airflow ratio z and Reynolds number on entropy generation.
Figure 10. Effect of airflow ratio z and Reynolds number on entropy generation.
Energies 14 06399 g010
Figure 11. Effect of airflow ratio y and Reynolds number on thermohydraulic efficiency.
Figure 11. Effect of airflow ratio y and Reynolds number on thermohydraulic efficiency.
Energies 14 06399 g011
Figure 12. Effect of airflow ratio y and Reynolds number on entropy generation.
Figure 12. Effect of airflow ratio y and Reynolds number on entropy generation.
Energies 14 06399 g012
Figure 13. Pareto front and ultimate optimum solution selected by TOPSIS decision-making process.
Figure 13. Pareto front and ultimate optimum solution selected by TOPSIS decision-making process.
Energies 14 06399 g013
Table 1. Summary of multi-pass SAH studies on flow pattern change.
Table 1. Summary of multi-pass SAH studies on flow pattern change.
Investigators (Year)Flow PatternHeat Transfer EnhancementMain Finding
Ho et al., 2013 [10] Energies 14 06399 i001Wire meshOptimal recycle ratio of 1.0
Yeh and Ho, 2013 [11] Energies 14 06399 i002Longitudinal finCollector efficiency increased with recycle ratio
Singh and Dhiman, 2018 [12] Energies 14 06399 i003Wire mesh packingOptimal recycle ratio of 1.8
Ho et al., 2018 [13] Energies 14 06399 i004Corrugated absorber and back platesOptimal recycle ratio of 0.5
Abo-Elfadl et al., 2020 [14] Energies 14 06399 i005Pin finIn total, 66.7% of air supply at the second pass exhibited the highest energy and exergy efficiencies
Ahmadkhani et al., 2021 [15] Energies 14 06399 i006Packed bed matrixRecycle flow to back plate (upper figure) led to higher air temperature rise
Table 2. Input parameters.
Table 2. Input parameters.
ParameterValueReference
Thermal conductivity of finks = 50.2 Wm−1K−1[19]
Fin thicknesst = 0.95 mm[19]
Number of finsn = 20-
Fin heightWf = 10 mm-
Collector lengthL = 2.1 m[16]
Collector widthW = 0.54 m[16]
Collector depthD = 0.021 m[16]
Solar radiationI = 848 W/m2[16]
Ambient temperatureTa = 27 °C[16]
Absorptivity of glass coversαγ1 = αγ2 = 0.05[16]
Absorptivity of absorber plateαπ = 0.92[16]
Emissivity of glass coversεγ1 = εγ2 = 0.92[16]
Emissivity of absorber plateεπ = 0.92[16]
Emissivity of back plateεβ = 0.92-
Transmissivity of glass coversτγ1 = τγ2 = 0.84[19]
Effective transmittance–absorptance productτα = 0.78[28]
Wind velocityVw = 1 m/s-
Increment in x-coordinateΔξ = 0.21 μ-
Stefan’s constantσ = 5.67⋅108 Ω/(μ2Κ4)-
Table 3. Range of key parameters.
Table 3. Range of key parameters.
Key ParameterRange
Reynolds number in the third passRe3 = 8000–18,000
Airflow ratio in the second passy = 0–0.4
Airflow ratio in the third passz = 0–0.4
Table 4. Parameters of the multi-objective optimization genetic algorithm.
Table 4. Parameters of the multi-objective optimization genetic algorithm.
ParameterValueRemark
Population size260Very large population size results in long computation time
Crossover fraction0.8Matlab manual and thermal research [33] recommend the value to obtain the best result
Pareto fraction0.35Default value
Maximum number of generations200 × number of variablesSensitivity analysis revealed that the Pareto frontier is reached after 121 iterations
Mutation functionAdaptive feasibleDue to bounds, used as shown in Table 3
Selection typeTournamentEnhances chance of selection for the fittest individual [33]
Crossover functionIntermediateDefault crossover function
Population typeDouble vectorThe individuals owned type double (not string)
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Phu, N.M.; Tu, N.T.; Hap, N.V. Thermohydraulic Performance and Entropy Generation of a Triple-Pass Solar Air Heater with Three Inlets. Energies 2021, 14, 6399. https://0-doi-org.brum.beds.ac.uk/10.3390/en14196399

AMA Style

Phu NM, Tu NT, Hap NV. Thermohydraulic Performance and Entropy Generation of a Triple-Pass Solar Air Heater with Three Inlets. Energies. 2021; 14(19):6399. https://0-doi-org.brum.beds.ac.uk/10.3390/en14196399

Chicago/Turabian Style

Phu, Nguyen Minh, Ngo Thien Tu, and Nguyen Van Hap. 2021. "Thermohydraulic Performance and Entropy Generation of a Triple-Pass Solar Air Heater with Three Inlets" Energies 14, no. 19: 6399. https://0-doi-org.brum.beds.ac.uk/10.3390/en14196399

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop